DualConnect™ Standard Features Include:
- Key Interlock with permanent generator and DPDS portable generator cable access door*
- Easy access cam lock locations for ease of cable connection
- Circuit breakers standard, molded case switches optional
- Type 3R powder-coated steel enclosure
(stainless steel & colors optional) - Hinged, padlockable access doors with door stops
- Hinged lower cover secures cord entries when not in use
- 3-pole circuit breakers standard (4-pole circuit breakers optional)
- 0 breaker, 1 breaker and 2 breakers available
- UL /cUL 1008 Listed up to 5000A
- NEC700.3(f) and NEC 240.87 compliant depending on configuration requested
*Two-breaker 5000A unit is interlocked with the portable generator breaker in the DPDS
DualConnect Optional Features:
- Phase monitor
- Utility ON indicator (unit mounted)
- 4-pole disconnects (switched neutral)
- Terminal strip (for devices like remote generator start, remote monitoring)
- Heaters with thermostat and de-humidistat
- 20A, 30A & 50A 125VAC or 240VAC twist-lock receptacles (for battery chargers, heaters)
- GFCI, Duplex & other receptacle connections available
- SCADA (Supervisory Control and Data Acquisition to connect to a PLC)
- Aux contacts
- Shunt trips
NEC 700.3 (F) – LEARN HOW RECENT NEC CHANGES MAY AFFECT YOUR BUSINESS, AND HOW ESL CAN HELP!